how to install ammonia detector in liquid ammonia storage tank for cold storage?

May 21, 2021 Leave a message

Ammonia leakage alarm detector can monitor the use of ammonia gas or production in industrial production quickly,When the gas concentration reaches the alarm value set by ammonia detector,it will make alarm to prompt the on-site staff to take necessary protective measures, which can effectively prevent the occurrence of ammonia poisoning accidents.

ammonia detector


Matters needing attention during installation and application of ammonia leakage alarm:

Once the ammonia leakage alarm detector is installed in place, its position is not easy to change. The following points should be considered during installation and application.


(1) Find out the possible leakage points of the devices to be monitored, analyze their leakage pressure, direction and other factors, and draw the distribution diagram of the probe position. According to the severity of the leakage, it can be divided into three grades: I, II and III. Location and number of detectors installed.


(2) According to the air flow direction, wind direction and other specific factors in the place, the leakage direction of toxic gas is judged when a large number of leakage occurs. The instrument should be installed in the down direction of wind direction to detect the leakage concentration of gas.


(3) According to the density of the leakage gas (greater or less than air), combined with the air flow trend, the three-dimensional flow trend diagram of the leakage is synthesized, and the initial setting scheme is made at the downstream position of the flow. Ammonia is lighter than air. If there is leakage, it will float to the upper part of the space. The ammonia leakage alarm device should be installed above the ammonia leakage source of the compressor. For places where toxic gas is easy to accumulate, special attention should be paid to the setting of safety monitoring points.


(4) We study whether the leakage state of the leakage point is micro leakage or spray. If it is a micro leak, the setting point should be close to the leak point. In case of spray leakage, keep away from the leakage point. Based on these conditions, the final setting scheme is worked out. In this way, the quantity and variety to be purchased can be estimated.


(5) For places with large toxic gas leakage, according to relevant regulations, a detection point should be set every 10-20m. For unattended small and discontinuous operation pump room, it is necessary to pay attention to the possibility of toxic gas leakage. Generally, a detector should be installed at the lower air outlet, which should not be greater than 3m indoors and 5m outdoors.


(6) For the open toxic gas diffusion and escape environment, if there is no good ventilation conditions, it is easy to make the toxic gas content in the air of a certain part close to or reach the lower explosion limit concentration. These are safety monitoring points that can not be ignored. According to the analysis results of field accidents, more than half of them are caused by incorrect installation and calibration. Therefore, it is necessary to introduce the correct installation and calibration precautions to reduce the failure.