Natural gas detector's installation location, installation angle, protective measures and system wiring and other aspects should prevent electromagnetic interference
Combustible gas alarm detector is used to check whether there is a gas leak and reminder people, so it i must be in good contact with the environment.

When there is combustible or toxic gases leak in industrial environment, a gas detector can make alarm when the concentration of toxic gases in the air reaches the critical point of explosion or poisoning alarm.If users do not pay attention to the maintenance, the combustible gas alarm will be blocked, resulting in errors or no detection of the situation.So regular cleaning and maintenance is the best effective way to prevent the failure. so the environment is very important,we must do a good job in maintaining before installing the combustible gas alarm as well as pay attention to check carefully and avoid omissions in small details.

The installation location of natural gas alarm detector is within 1.5 meters from the gas source radius, and in well-ventilated places.
(1) natural gas, city gas and carbon monoxide are lighter than air, which are installed about 0.3 meters from the ceiling.
(2) LPG is heavier than air and is installed about 0.3 meters away from the ground.(1) the probe of natural gas alarm is mainly the detection element that contacts the combustion gas sensor. It is composed of a ball of aluminum oxide and adhesive coated on the platinum wire coil, and its outer surface is covered with platinum, palladium and other rare metals.Therefore, must take care during installation to avoid damage.(2) the installation height should be generally 160 -- 170cm, which is easy for maintenance.
(3) natural gas detector is a safety instrument, with sound, light, display function,so it should be installed in the staff easy to see and easy to hear, so as to eliminate hidden dangers in time.
(4) the natural gas detector should not have a strong electromagnetic field (such as high-power motor, transformer) around.
(5) the installation position should be different with different density of measured gas
Our gas alarm detector products include: gas alarm, natural gas alarm, liquefied gas alarm, hydrogen alarm, methane alarm, acetylene alarm, etc.Toxic gas alarm: ammonia alarm, chlorine alarm, carbon monoxide alarm, hydrogen sulfide alarm, carbon dioxide alarm, etc.Products are sold around the world, they are suitable for oil refineries, chemical plants, liquefied gas station, gas boiler room, refueling gas station, paint room and other use of flammable industrial sites, with CE, ATEX, Explosion proof.